Fire Alarm Installation Methods Study Guide

1. Codes, Standards & Documentation

Standard/CodeApplication
NFPA 72System design, installation, maintenance
UL 268Smoke detectors
UL 1971Strobe signals for hearing impaired
NEC Art. 760Wiring/fire alarm circuits

2. Fire Alarm Control Units & Power

Power ProblemAction
AC LossBattery backup takes over, trouble signal activates
Battery won't chargeReplace if not recharged in 48 hours

3. Circuit Classes & Supervision

Circuit TypeFunctionKey Feature
IDCInitiating devicesEOL resistor, supervision
NACNotification appliancesEOL resistor, voltage drop
SLCAddressable devicesPolling, device ID

4. Initiating Devices & Spacing

DeviceSpacing/Location
Smoke Detector30’ centers (typ.), near peak/ceiling
Heat DetectorPer mfg/NFPA, reduce if ceiling >10’
Pull StationMax 48” height, within 200’ of all exits

5. Notification Appliances

ApplianceStandard
StrobeUL 1971
Horn/SpeakerUL 464

6. Wiring, Cable, & Installation

Cable MarkingUse
FPLPPlenum rated
FPLRRiser rated
FPLGeneral purpose
CL2RClass 2, riser rated

7. Inspection, Testing, & Maintenance

TestPurpose
Sensitivity test (smoke)Ensure within mfg. range
Heat detectorTest with heat gun per mfg.
Battery testLoad test annually

8. Quick Reference & Best Practices

SignalDescription
AlarmFire event, highest priority
TroubleFault that may impair operation
SupervisoryNon-fire condition (e.g. closed valve)