National Electrical Code (NFPA 70)
Comprehensive Study & Field Reference

1. Scope & Fundamentals

2. Definitions & Key Articles

TermDefinitionCode Article
Branch Circuit Conductors between final overcurrent device and outlets Art. 100, 210
Feeder Between service equipment and branch circuit panels Art. 100, 215
Service Entrance conductors and equipment to utility supply Art. 100, 230
Grounded (Neutral) Conductor System conductor intended to carry current under normal operation Art. 100, 200
Bonding Permanent joining of conductive parts to ensure continuity Art. 100, 250
Overcurrent Device Protects circuit by opening when current is excessive Art. 100, 240
Raceway Enclosed channel (conduit, tray, duct, etc.) Art. 100, 300

3. Wiring Methods & Materials

Cable/ConduitCommon UsesNotes
NM (Romex)Dry, residential onlyNot in wet or exposed
MCCommercial, exposed, some wetMust be listed, armor is not ground
EMTConduit, indoor/commercialNot for direct burial
PVCUnderground, wet areasMust be sunlight-resistant, sch. 40/80
Installer Tip: Mark all wires at terminations. Never strip more than code allows; all unused box knockouts must be plugged.

4. Conduit, Raceway & Box Fill

Wire GaugeSingle Device Box (cu in)Double Device Box (cu in)
#141830
#122032
#102234

5. Cable Types, Uses & Markings

Exam Note: All wire splices must be in accessible junction boxes – no buried splices allowed.

6. Grounding & Bonding

Safety: “Bootleg” grounds (neutral-to-ground jumpers in subpanels) are a major code violation and shock hazard!

7. Services, Feeders, Branch Circuits

Room/AreaGFCI?AFCI?
BathroomYesNo
KitchenYes (all counters)Yes
BedroomNoYes
GarageYesNo
OutdoorYesNo
Field Tip: All OCPDs must be marked for “series rating” if used for that purpose. Never install larger breaker “just to stop nuisance trips.”

8. Load Calculations

CalculationFormula/Notes
Service/feeder size (A) Total VA ÷ voltage ÷ 0.8 (for continuous load)
Branch circuit min size Load (A) × 1.25 for continuous, plus largest motor
VA to amps (single phase) VA ÷ volts = A
VA to amps (three phase) VA ÷ (volts × √3) = A
Exam Example: 1200 ft² house, 3 VA/ft² = 3600 VA, plus kitchen/laundry circuits, appliances, HVAC, water heater, etc.

9. Low Voltage & Fire Alarm (Art. 725, 760, 770)

Fire Alarm Tip: Use EOL (end-of-line) resistors for zone supervision on Class B circuits. See your fire alarm plans and NFPA 72 for spacing and device requirements!

10. Boxes, Devices & Special Occupancies

Inspection: “No ground wire in box” = automatic fail. Hospital, commercial kitchens, and hazardous locations require special hardware and inspection.

11. Inspection, Testing & Safety

Field Safety: “Test before you touch.” Never trust a label or someone else’s word—verify de-energized with a meter.

12. Examples, Field Scenarios & Quick Reference

Example 1: Branch Circuit Design (Residential)

Example 2: Fire Alarm NAC in Conduit

Example 3: Grounding/Bonding in Subpanel

Example 4: MC Cable in Commercial Ceiling

Example 5: Voltage Drop Calculation (Lighting Circuit)

Quick Reference

RequirementNEC ValueField Note
Service Ground Rod 8 ft min, ≤25Ω or supplement Always use two rods unless you test!
Panel Working Space 36" deep × 30" wide × 78" high No storage in working space
Outlet Box Fill 2.0 cu in (#14), 2.25 cu in (#12) Each device = 2x wire fill
Conductor Ampacity See Table 310.16 Adjust for ambient, # of wires
Minimum burial depth 18" for direct burial, 24" for PVC Check local amendments!