Term | Definition | Code Article |
---|---|---|
Branch Circuit | Conductors between final overcurrent device and outlets | Art. 100, 210 |
Feeder | Between service equipment and branch circuit panels | Art. 100, 215 |
Service | Entrance conductors and equipment to utility supply | Art. 100, 230 |
Grounded (Neutral) Conductor | System conductor intended to carry current under normal operation | Art. 100, 200 |
Bonding | Permanent joining of conductive parts to ensure continuity | Art. 100, 250 |
Overcurrent Device | Protects circuit by opening when current is excessive | Art. 100, 240 |
Raceway | Enclosed channel (conduit, tray, duct, etc.) | Art. 100, 300 |
Cable/Conduit | Common Uses | Notes |
---|---|---|
NM (Romex) | Dry, residential only | Not in wet or exposed |
MC | Commercial, exposed, some wet | Must be listed, armor is not ground |
EMT | Conduit, indoor/commercial | Not for direct burial |
PVC | Underground, wet areas | Must be sunlight-resistant, sch. 40/80 |
Installer Tip: Mark all wires at terminations. Never strip more than code allows; all unused box knockouts must be plugged.
Wire Gauge | Single Device Box (cu in) | Double Device Box (cu in) |
---|---|---|
#14 | 18 | 30 |
#12 | 20 | 32 |
#10 | 22 | 34 |
Exam Note: All wire splices must be in accessible junction boxes – no buried splices allowed.
Safety: “Bootleg” grounds (neutral-to-ground jumpers in subpanels) are a major code violation and shock hazard!
Room/Area | GFCI? | AFCI? |
---|---|---|
Bathroom | Yes | No |
Kitchen | Yes (all counters) | Yes |
Bedroom | No | Yes |
Garage | Yes | No |
Outdoor | Yes | No |
Field Tip: All OCPDs must be marked for “series rating” if used for that purpose. Never install larger breaker “just to stop nuisance trips.”
Calculation | Formula/Notes |
---|---|
Service/feeder size (A) | Total VA ÷ voltage ÷ 0.8 (for continuous load) |
Branch circuit min size | Load (A) × 1.25 for continuous, plus largest motor |
VA to amps (single phase) | VA ÷ volts = A |
VA to amps (three phase) | VA ÷ (volts × √3) = A |
Exam Example: 1200 ft² house, 3 VA/ft² = 3600 VA, plus kitchen/laundry circuits, appliances, HVAC, water heater, etc.
Fire Alarm Tip: Use EOL (end-of-line) resistors for zone supervision on Class B circuits. See your fire alarm plans and NFPA 72 for spacing and device requirements!
Inspection: “No ground wire in box” = automatic fail. Hospital, commercial kitchens, and hazardous locations require special hardware and inspection.
Field Safety: “Test before you touch.” Never trust a label or someone else’s word—verify de-energized with a meter.
VD = 2 × K × I × D / CM
Requirement | NEC Value | Field Note |
---|---|---|
Service Ground Rod | 8 ft min, ≤25Ω or supplement | Always use two rods unless you test! |
Panel Working Space | 36" deep × 30" wide × 78" high | No storage in working space |
Outlet Box Fill | 2.0 cu in (#14), 2.25 cu in (#12) | Each device = 2x wire fill |
Conductor Ampacity | See Table 310.16 | Adjust for ambient, # of wires |
Minimum burial depth | 18" for direct burial, 24" for PVC | Check local amendments! |
VD = 2 × K × I × D / CM