Type | Description | Exam Tip |
Initiating Device |
Smoke/heat/manual/waterflow, detects hazard |
Requires zone/address, must be supervised |
Notification Appliance |
Warns (horn/strobe/speaker/bell) |
Strobes must be synchronized in same area |
Supervisory |
Valve closed, air pressure, temperature |
Yellow light, distinct from alarm |
Trouble |
Open, short, ground, battery, device fault |
Must annunciate within 200 seconds |
Class | Description | Fault Tolerance | Typical Use |
A |
Loop with return path to panel (four wires) |
Single open does not disable devices; both sides needed for full operation |
Critical detection (addressable SLC) |
B |
One-way loop (two wires) |
Single open disables devices past the break |
Conventional detection |
C |
Multiple pathways, point-to-point |
Single open may/may not disable devices |
Special signaling, usually not used for detection |
D |
Fault-tolerant via redundancy, diversity |
Survives any single open or short |
High reliability (e.g., military) |
Trouble Signal | Likely Causes | Solution |
Open Circuit |
Wire cut, EOL missing, device removed |
Check continuity, replace EOL, inspect wiring/devices |
Short Circuit |
Wires crossed, device/panel failure |
Isolate by zone/section, replace shorted cable/device |
Ground Fault |
Wire touching ground/metal, water intrusion |
Megger or ground-fault meter, isolate branch |
Device Fault |
Dirty detector, missing base, wrong address |
Clean, readdress, replace device |
Low Battery |
Failed battery, charging issue |
Replace battery, test charger |
Requirement | NFPA 72 Standard Value | Field Note |
Max. pull station spacing |
200 ft travel distance |
Each exit, each floor, 42–48" AFF |
Smoke detector spacing |
Max 30 ft apart |
Adjust for ceiling height, airflow |
Sound level, general area |
≥15 dBA above ambient |
75 dBA at pillow in sleeping rooms |
Strobe mounting height |
80–96" above floor |
Wall/ceiling labeled for use |
Battery standby |
24 hr + 5 min alarm (15 min voice evac) |
Multiply by 1.25 for margin |
NAC voltage drop |
End-of-line ≥ device minimum (16V) |
Use voltage drop formula; recalc for long circuits |
Record retention |
Next test + 1 year |
Keep on-site for AHJ |
Ground fault trouble |
Annunciate in ≤200s |
Panel should indicate which circuit |