NFPA 72 Fire Alarm & Signaling Code – Deep Reference & Exam Study Guide

1. Scope & Fundamentals

2. Essential Terms & System Types

Initiating Device
Component that detects fire, smoke, heat, or manual action. Includes smoke, heat, duct, waterflow, manual pulls, and more.
Notification Appliance
Device that notifies occupants: horns, strobes, speakers, bells, chimes.
Addressable System
Each device has a unique identifier for location/troubleshooting; shows specific device status on the panel.
Conventional (Zoned) System
Devices wired in parallel; panel shows zone/area, not specific device.
Class A/B Circuits
Class A: loops with return path, survive single break; Class B: simple loop, downstream fail on open.
Pathway Survivability Levels
Level 0: none. Level 1: 2-hour protection. Level 2: redundant or 2-hr + separated. Level 3: 2-hr, fully separated, redundant risers (e.g. high-rise voice evac).
Supervisory Signal
Signals non-fire issue (sprinkler valve closed, air pressure low, etc.).
Trouble Signal
Indicates wiring, device, battery, or ground fault.
Alarm Verification
Panel delays alarm for short period (e.g., 30s) to verify transient signals before full alarm.
Silence Function
Allows horns/bells to be silenced; strobes continue to flash until reset.
TypeDescriptionExam Tip
Initiating Device Smoke/heat/manual/waterflow, detects hazard Requires zone/address, must be supervised
Notification Appliance Warns (horn/strobe/speaker/bell) Strobes must be synchronized in same area
Supervisory Valve closed, air pressure, temperature Yellow light, distinct from alarm
Trouble Open, short, ground, battery, device fault Must annunciate within 200 seconds

3. Documentation & Submittals

Field Note: AHJs will frequently reject plans that do not show room names/numbers, device addresses, or sequence of operations clearly. "Missing details = failed permit!"

4. Power Supply & Battery Calculations

5. Circuits, Classes, Pathways

ClassDescriptionFault ToleranceTypical Use
A Loop with return path to panel (four wires) Single open does not disable devices; both sides needed for full operation Critical detection (addressable SLC)
B One-way loop (two wires) Single open disables devices past the break Conventional detection
C Multiple pathways, point-to-point Single open may/may not disable devices Special signaling, usually not used for detection
D Fault-tolerant via redundancy, diversity Survives any single open or short High reliability (e.g., military)

6. Initiating Devices

Manual Devices

Automatic Devices

Exam Tip: Know where smoke detectors are NOT required: mechanical rooms (unless required by AHJ), bathrooms with shower/tub, non-habitable attics/closets.

7. Notification Appliances

Audible Notification

Visible Notification (Strobes)

Space TypeMin. Sound LevelStrobe Candela
Sleeping Room75 dBA at pillow110 cd at bed
General Area15 dBA over ambient15 cd (public); 75–110 cd (large)
Restroom15 dBA over ambient75 cd
Field Tip: Don't mount strobes next to strong lighting or in direct sunlight—flash may not be visible in those conditions.

8. Supervision, Integrity, and Troubleshooting

Trouble SignalLikely CausesSolution
Open Circuit Wire cut, EOL missing, device removed Check continuity, replace EOL, inspect wiring/devices
Short Circuit Wires crossed, device/panel failure Isolate by zone/section, replace shorted cable/device
Ground Fault Wire touching ground/metal, water intrusion Megger or ground-fault meter, isolate branch
Device Fault Dirty detector, missing base, wrong address Clean, readdress, replace device
Low Battery Failed battery, charging issue Replace battery, test charger

9. Inspection, Testing & Maintenance

Device/ComponentInspection/Test Frequency
Smoke DetectorsAnnual functional test; semiannual sensitivity test
Manual Pull StationsAnnual
Sprinkler Waterflow SwitchesQuarterly (wet), semiannual (dry)
Notification AppliancesSemiannual (visible), annual (audible)
Control PanelMonthly (visual), annual (function)
BatteriesMonthly (visual), annual (load test)

10. Emergency & Mass Notification

Field Example: In a 12-story apartment, an EVACS must deliver clear evacuation instructions on all floors, with automatic message repeats every 2 minutes until reset.

11. Interfaces & Special Features

Installer Note: All interfaces must be tested and witnessed by AHJ and owner; simulated fire alarm must cause all required functions to operate as intended.

12. Practical Examples & Field Scenarios

Example 1: School Fire Alarm Upgrade

Example 2: High-Rise Voice Evac

Example 3: Warehouse NAC Voltage Drop

Example 4: Assisted Living Facility Testing

Example 5: Restaurant Remodel

13. Quick Reference Tables, Tips & Formulas

RequirementNFPA 72 Standard ValueField Note
Max. pull station spacing 200 ft travel distance Each exit, each floor, 42–48" AFF
Smoke detector spacing Max 30 ft apart Adjust for ceiling height, airflow
Sound level, general area ≥15 dBA above ambient 75 dBA at pillow in sleeping rooms
Strobe mounting height 80–96" above floor Wall/ceiling labeled for use
Battery standby 24 hr + 5 min alarm (15 min voice evac) Multiply by 1.25 for margin
NAC voltage drop End-of-line ≥ device minimum (16V) Use voltage drop formula; recalc for long circuits
Record retention Next test + 1 year Keep on-site for AHJ
Ground fault trouble Annunciate in ≤200s Panel should indicate which circuit